The MGate 5123 is an industrial Ethernet gateway for converting CANopen or J1939 to PROFINET network communications. To integrate existing
CANopen or J1939 devices onto a PROFINET network, use the MGate 5123 as a CANopen or J1939 master to collect data and exchange data with
the PROFINET IO controller. All models are protected by a rugged and compact metal housing and are DIN-rail mountable. The rugged design is
suitable for industrial applications such as factory automation and other process automation industries.
Easy Configuration
The MGate 5123 gateways are provided with a web console to make configuration easy without having to install an extra utility. In addition, HTTPS
encryption of communication ensures higher network security.
In most data-acquisition applications, the configuration of CANopen devices can be time-consuming and increase costs. The MGate 5123 gateways
provide EDS file import function and the user can auto-scan the CANopen devices to help complete the settings quickly. The MGate gateways provide
software-configurable termination resistor settings for CANbus to reduce efforts by eliminating the need to open the chassis.
Easy Troubleshooting
The MGate 5123 gateways provide a variety of maintenance functions to reduce troubleshooting time and cost, including LED indicators, protocol
diagnostics, traffic monitoring, and tag view. These tools help you capture and check data to easily identify the root cause of issues, especially during
the installation stage. The MGate gateways also come with status monitoring and fault protection functions. The status monitoring function notifies
a PLC/DCS/SCADA system when a CAN device gets disconnected or does not respond, in which case the process PLC/DCS gets the status of
each end device and then issues alarms to notify operators. The fault protection function executes actions pre-defined by the user when a host
gets disconnected to prevent the end devices from going offline for long periods of time.
You can also find the MGate 5123-T model in the MGate 5123 Series.
You can buy the MOXA MGate 5123 CANopen/J1939-to-EtherNet/IP Gateway online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.
Certifications
Features
- Simultaneous protocol conversions from CANopen and J1939 to PROFINET and SNMP
- Supports PROFINET I/O device and SNMP agent
- Supports CANopen master and J1939
- Flexible deployment with Ethernet cascading and dual subnet
- Embedded traffic monitoring/diagnostic information for easy troubleshooting
- Easy device configuration via a web-based console
- microSD card for configuration backup/duplication
- Supports dual redundant DC power inputs and 1 relay output
- CAN port with 2-kV isolation protection
- Developed according to IEC 62443-4-2 with Secure Boot
CAN to PROFINET Gateway : Ethernet Interface | |
Ports | 2 x 10/100BaseT(X) Ports (RJ45 connector) |
Magnetic Isolation Protection | 1.5 kV (built-in) |
Industrial Protocols | PROFINET IO Device |
Authentication | Local database |
Encryption | HTTPS, AES-128, AES-256, SHA-256 |
Security Protocols | SNMPv3, SNMPv2c Trap, HTTPS (TLS 1.3) |
CAN to PROFINET Gateway : CAN Interface | |
Ports | 1 x Spring-type Euroblock terminal |
Standards | ISO 11898-2 |
Baudrate | CANopen: 10 kbps, 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 800 kbps, 1 Mbps; J1939: 250 kbps, 500 kbps, 1 Mbps |
Max No. of Transmit PDOs | 256 |
Terminator | 120 ohms, software configurable |
Signals | CAN_H, CAN_L, GND, Ext_CAN_H, Ext_CAN_L, CAN_Shield |
Industrial Protocols | CANopen master, J1939 |
CAN to PROFINET Gateway : CANopen | |
Max No. of Nodes | 64 |
Max No. of Receive PDOs | 256 |
SDOs | Supported |
Input Data Size | 2048 bytes |
Output Data Size | 2048 bytes |
CAN to PROFINET Gateway : J1939 | |
Max. No. of Commands | 256 |
Input Data Size | 2048 bytes |
Output Data Size | 2048 bytes |
CAN to PROFINET Gateway : PROFINET | |
MicroSD Slot | Up to 32 GB (SD 2.0 compatible) |
Mode | IO Device class B |
Max. No. of Master Connections | 2 IO controllers (shared devices) |
Input Data Size | 1440 bytes (bytes per IO Controller, total: 2880 bytes) |
Output Data Size | 1440 bytes (bytes per IO Controller, total: 2880 bytes) |
CAN to PROFINET Gateway : Power Parameters | |
Input Voltage | 12 to 48 VDC |
Input Current | 455 mA (max) |
Power Connector | Spring-type Euroblock terminal |
CAN to PROFINET Gateway : Physical Characteristics | |
Housing | Metal |
IP Rating | IP30 |
Dimensions | 25 x 90 x 129.6 mm (0.98 x 3.54 x 5.1 in) |
Weight | 294 g (0.65 lb) |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
CAN to PROFINET Gateway : Standards and Certifications | |
Safety | EN 61010-2-201, UL 61010-2-201 |
EMC | EN 61000-6-2/-6-4 |
EMI | FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV, IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m, IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV, IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV, IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m, IEC 61000-4-8 PFMF |
Shock | IEC 60068-2-27 |