Introduction
The MGate 5135 /5435 gateways are 1- and 4-port industrial Ethernet gateways, respectively for Modbus RTU/ASCII/TCP and EtherNet/IP network communications. To integrate existing Modbus devices onto an EtherNet/IP network, use the MGate 5135/5435 gateway as a Modbus client to collect data and exchange data with the EtherNet/IP host. All models are protected by a rugged and compact metal housing, are DIN-rail mountable, and offer built-in serial isolation. The rugged design is suitable for industrial applications such as factory automation, power, oil and gas, water and wastewater, and other process automation industries.
You can buy the MOXA MGate 5435-T Industrial Ethernet Gateways, which is applicable in Oil & Gas, Power Utility, Water & Wastewater industries, online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.
Certifications
Features
- Modbus RTU/ASCII/TCP-to-EtherNet/IP gateways
- 2 10/100BaseT(X) Ports (RJ45 connector)
- 4 RS-232/422/485 Serial Port
- 12 to 48 VDC input power
- Metal body
- -40 to 75°C operating temperature
industrial gateway : Ethernet Interface | |
Number of Ports | 2 |
Speed | 10/100BaseT(X) Ports (RJ45 connector) Auto MDI/MDI-X connection |
Connector | RJ45 connector |
Magnetic Isolation Protection | 1.5 kV (built-in) |
Modbus TCP | Mode: Client, Functions Supported: 1, 2, 3, 4, 5, 6, 15, 16, 23, Max. No. of Server Connections: 32, Max. No. of Commands: 128, Total Input & Output Data Size: 4000 bytes |
PROFINET | - |
EtherNet/IP | Mode: Adapter, CIP Objects Supported: Identity, Message Router, Assembly, Connection Manager, TCP/IP interface, Ethernet link, Port, Max. No. of Scanner Connections: 4 (read/write), Input & Output Data Size: 496 bytes/connection (total: 3968 bytes) bytes |
Protocols | Modbus TCP Client, EtherNet/IP Adapter |
industrial gateway : Serial port specifications | |
Flow Control | RTS Toggle (RS-232 only), RTS/CTS |
Protocol | Modbus RTU/ASCII Client |
RS-232 Signals | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
Number of Ports | 4 |
RS-422 Signals | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-4w Signals | Tx+, Tx-, Rx+, Rx-, GND |
Serial Standards | RS-232/422/485 |
Connectors | DB9 male |
RS-485-2w Signals | Data+, Data-, GND |
RS-485 Data Direction Control | ADDC (automatic data direction control) |
Pull High/Low Resistor for RS-485 | 1 kilo-ohm, 150 kilo-ohms |
Terminator for RS-485 | 120 ohms |
Isolation | 2 kV (built-in) |
industrial gateway : Serial Communication Parameters | |
Data Bits | 7, 8 |
Stop Bits | 1, 2 |
Parity | Even, Odd, Space, Mark, None |
Baudrate | 300 bps to 921.6 kbps |
industrial gateway : Software | |
Configuration Options | Web Console (HTTPS), Device Search Utility (DSU) |
Utility | - |
Support | - |
industrial gateway : General | |
MTBF | 689,989 hrs hrs |
industrial gateway : Power Requirements | |
Input Current | 455 mA (max): 12 to 48 VDC |
Input Voltage | 12 to 48 VDC |
Power Connector | Spring-type Euroblock terminal |
industrial gateway : Physical Characteristics | |
Dimensions | 42 x 90 x 130 mm (1.65 x 3.54 x 5.1 in) |
Housing | Metal |
Operating Temperature | -40 to 75°C (-40 to 167°F) |
Weight | 403 g (0.89 lb) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Vibration | IEC 60068-2-6, IEC 60068-2-64 |
Shock | IEC 60068-2-27 |
Drop | IEC 60068-2-31 |
Safety | EN 61010-2-201, UL 61010-2-201 |
Hazardous Location | - |
EMC | EN 61000-6-2/-6-4 |
EMI | FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m IEC 61000-4-8 PFMF |
Storage Card Slot | - |